details__small-images
details__small-images

Eaton DXRT Online UPS (6-10kW)

Brand: Eaton

Eaton DX-RT is a true online double conversion Rack and Tower Convertible UPS system that affordably provides Robust, Reliable, Compact and Efficient Power Management Solution for Mission Critical Application from downtime, data-loss. Eaton DX-RT delivers more power in a limit space (2U) and saves energy cost due to it’ highly efficiency design and offers efficiency upto 95% in online mode.

Eaton DX-RT perfectly fits harsh Indian environmental and power condition and Provide much stronger protection on inrush current and it improves it’s adaptability to grid power condition

Request Quote
  • 2 years of Eaton factory warranty support
    • Typical Applications
    • Networking and Server Equipment
    • Small and Micro Data Centre application
    • Bio-Metrics/Radiology and Medical Equipment
    • Security and Surveillance System/CCTV and CAMERA
    • Printer/IT-Load and PCs
    • Industrial and buildings critical power backup requirement
    • Core Features
    • IGBT Based Rectifier True Online Double Conversion
    • New Graphical LCD Display
    • Rack & Tower Convertible, Higher power density (only 2U and <600mm depth for 10K)
    • Wide Input Voltage window (110 – 275Vac) for Indian Environmental Condition
    • Double Conversion Efficiency up to 95%
    • Active Input Power Factor Correction 0.99
    • Unity Output Power Factor
    • Inbuilt OVCD (Over Voltage Cut-off Device)
    • Generator Compatible with Wide Input Voltage window
    • Frequency Range (40 Hz-70 Hz)
    • Digital Charger Technology provides 0-12 A charging current
    • Adjustable Battery numbers 16/17/18/19 and 20
    • 50/60 Hz Automatic Frequency Converter Mode
    • WINPOWER software support virtualization transfer application Intelligent Monitoring options
    • High Performance
    • kVA=kW
    • Rack and Tower Convertible
    • Form Factor 2U with <600 mm Depth
    • True Input PF 0.99
    • True output Unity PF 1
    • Input THDi 3%
    • Output THDv 1%
    • Higher Power Density
    • Higher Efficiency up to 95%
    • Support Critical Virtualization
    • High Reliability and Adaptability
    • Wide Input Voltage Range
    • Inbuilt Hardware Current Limit Technology
    • Upgraded Phase Lock Algorithm
    • Inbuilt Over-voltage Cut-off Device
    • Inbuilt Over Temperature Protection
    • Up to 50 Degree Celsius operation @50% Load (Specific to XL Model)
    • Better Overload Protection up to 105% Constant

    Specification

    Model Name DXRT6K-IN DXRT6KS-IN DXRT10K-IN DXRT10KS-IN
    Catalog Number 9104-1229KX 9104-1229KXS1 9104-1229KXT1 9104-1229KXTS1
    UPC Code 743172097103 743172097080 743172097097 743172097110
    Input Characteristics
    Acceptable Input Voltage 110VAC-275VAC
    Phase Single phase with ground
    Input voltage range to take 50% load 110VAC-275VAC
    Input voltage range to take 100% load 160VAC-275VAC
    Input Current Limit 46.5 A
    Input Power Factor ≥ 0.995
    Input Frequency Range 45-55Hz / 54-66Hz (extendable to 40-70Hz when load < 60%)
    Input Protection Upstream breaker
    Generator Set 1.5 x UPS Rating Power
    Output Characteristics
    Power (VA) max 6000 6000 10000 10000
    Power (W) max 6000 6000 10000 10000
    Power Factor 1.0
    Waveform Pure sine wave
    Nominal Voltage 208/220/230/240V
    Voltage Variation <1% THD linear load
    <5% (non-linear load)
    Synchronization Range 45-55Hz / 54-66Hz (extendable to 40-70Hz when load < 60%)
    Full Load Efficiency
    Line mode with battery full charged 96% @ 230V output with typical load
    eCO mode 98%
    Battery Characteristics
    Inner Battery Rating/Type 12V/7AH*16 (adjustable) NA 12V/9AH*16 (adjustable) NA
    External Battery Connection Connector
    Back-up Time (50% load) 11 minutes typical / 8 minutes typical /
    Back-up Time (70% load) 6.5 minutes typical / 5 minutes typical /
    Back-up Time (full load) 4.5 minutes typical / 3 minutes typical /
    DC Voltage 192VDC (192V-240V adjustable)
    Charger Current Default 1.4 A (0-14 A adjustable) Default 4.0 A (0-12 A adjustable) Default 2.0 A (0-12 A adjustable) Default 4.0 A (0-12 A adjustable)
    Floating Voltage Phase 13.65V/c
    Charging Time 3 hours to 90% with internal battery
    Features
    eCO Mode YES
    Battery Capacity Calculation YES
    Fan Speed Control YES
    Frequency Converter Mode (CVCF) YES, 60% load factory operation
    Maintenance Bypass Switch YES
    Parallel Optional (up to 3 units)
    Mechanical & Environmental Characteristics
    WxHxD (mm) 438*86*573 438*86*573 438*86*573 438*86*573
    Net Weight (kg) 13 13.1 14.7 15
    Wheels NO
    Operating Temperature Range 0°C ~ 40°C (+40°C for 50% load)
    Humidity 0 ~ 95% (No condensing)
    Audible Noise (@75% load, charger current 12A) ≤50dB